# Signal converter 1IN, 4OUT, 4-20mA Input, 4-20mA Output, 24VDC

> Industrial signal converter (ref. 88001) that distributes a single 4-20mA analog input signal to 4 galvanically isolated 4-20mA outputs, eliminating ground loops and interference. Accuracy 0.1% FS, response time

- Page: https://sigmanortec.ro/en/signal-converter-1in-4out-4-20ma-input-4-20ma-output-24vdc
- Price: 217.41 RON
- Availability: In stock; 1-2 zile
- Reference: 88001 · EAN: 5946505856665
- Category: Mechatronics and IoT > Adapters and Converters
- Specifications: Input Voltage: 24VDC; Input Voltage Type: “DC” in Romanian can mean **“de ce”**, which translates to **“why”** in English.
- Package (shipping data): 0.193 kg
- Updated: 2026-09-14
- Shop: [Sigmanortec.ro](https://sigmanortec.ro/en/llms.txt)
- Prices: RON, VAT included; prices and stock as of 2026-10-22 04:49 (Europe/Bucharest)

## Description

Industrial signal converter that distributes a single 4-20mA analog signal to four devices, maintaining measurement stability. Offers 4 galvanically isolated 4-20mA outputs to eliminate ground loops and interference, 0.1% FS accuracy and response time below 10 ms. 24VDC power supply, quick mounting on 35mm DIN rail.
Signal converter designed for industrial applications where it is necessary to distribute a 4-20mA analog signal to multiple equipment. The device takes a 4-20mA input signal and reproduces it in four separate outputs, preventing interference and ground loops, having galvanic isolation.
Installation is done on a standard 35mm DIN rail.
Specifications:
Power supply: 24VDC
Input signal: 4-20mA
Output: 4 x 4-20mA isolated outputs
Accuracy: 0.1% FS
Input impedance: <=50Ω
Load resistance: RL<=500Ω
Dielectric strength: 1500 VAC/1 min
Operating temperature: -20 - +55°C (humidity < 80%)
Response time: <=10 ms
Isolation type: galvanic isolation between input and output
Mounting: 35mm DIN rail
Weight: 140g
Dimensions: 114.5x100x22.5mm
Use
Power the converter (16 + and 15 -), connect the input signal (13 +; 9 S; 10 -) and the equipment to the output terminals (1 +, 2- ; 3 +, 4 -; 5 +, 6- ; 7 +, 8 -). Make sure that the device is properly powered and is mounted in a moisture-proof environment. Avoid exceeding the rated current of 20mA or the supply voltage of 24V to prevent damage to the device.
Login:
Step | Instruction | Connection details / precautions
1 | Converter power supply | Connect terminal 16 to +24V DC and terminal 15 to – (GND) .
2 | Input signal connection | 13 (+) – positive signal; 9 (S) – screen/ground signal; 10 (–) – negative signal.
3 | Connect output 1 | 1 (+) and 2 (–) to the first device.
4 | Connect output 2 | 3 (+) and 4 (–) to the second device.
5 | Connect output 3 | 5 (+) and 6 (–) to the third device.
6 | Connect output 4 | 7 (+) and 8 (–) to the fourth device.
7 | Power check | Confirm that the voltage is exactly 24V DC and the current on each channel does not exceed 20mA.