# Signal converter 2IN, 4OUT, 4-20mA Input, 4-20mA Output, 24VDC

> Industrial signal converter (ref. 88012) that distributes two analog 4-20mA signals to four isolated 4-20mA outputs (grouped in pairs). Powered by 24VDC, with galvanic isolation between input and output, accuracy 0.1% FS, response time

- Page: https://sigmanortec.ro/en/signal-converter-2in-4out-4-20ma-input-4-20ma-output-24vdc
- Price: 261.90 RON
- Availability: In stock; 1-2 zile
- Reference: 88012 · EAN: 5947531137094
- Category: Mechatronics and IoT > Serial and CAN Converters
- Specifications: Input Voltage: 24VDC; Input Voltage Type: “DC” in Romanian can mean **“de ce”**, which translates to **“why”** in English.
- Package (shipping data): 0.193 kg
- Updated: 2026-09-14
- Shop: [Sigmanortec.ro](https://sigmanortec.ro/en/llms.txt)
- Prices: RON, VAT included; prices and stock as of 2026-10-22 04:49 (Europe/Bucharest)

## Description

Distributes two 4-20mA analog signals to four devices, ideal for industrial automation where you need stable and interference-free replication. Offers galvanic isolation to eliminate ground loops, clear allocation of channels 1-2 and 3-4 on the two inputs, 0.1% FS accuracy and fast response under 10 ms, 24VDC power supply, 35 mm DIN rail mounting.
Signal converter designed for industrial applications where it is necessary to distribute two 4-20mA analog signals to multiple equipment. The device takes two 4-20mA input signals from different sensors and reproduces them in four separate outputs, preventing interference and ground loops, having galvanic isolation.
Input 1 controls outputs 1 and 2. Input 2 controls outputs 3 and 4.
Specifications:
Power supply: 24VDC
Input signal: 2 x 4-20mA
Output: 4 x 4-20mA isolated outputs (group of 2)
Accuracy: 0.1% FS
Input impedance: <=50Ω
Load resistance: RL<=500Ω
Dielectric strength: 1500 VAC/1 min
Operating temperature: -20 - +55°C (humidity < 80%)
Response time: <=10 ms
Mounting: 35mm DIN rail
Isolation type: galvanic isolation between input and output
Weight: 140g
Dimensions: 114.5x100x22.5mm
Use
Make sure the device is properly powered and mounted in a moisture-proof environment. Avoid exceeding the rated current of 20mA or the supply voltage of 24V to prevent damage to the device.
Login:
Step | Function | TERMINALS | Details
1 | Converter power supply | 16 (+24VDC), 15 (GND) | Stable supply voltage 24VDC
2 | Signal input 1 | 13 (+), 9 (S), 10 (–) | 4-20mA signal from sensor/device 1
3 | Signal input 2 | 14 (+), 11 (S), 12 (–) | 4-20mA signal from sensor/device 2
4 | Exit 1 | 1 (+), 2 (–) | Controlled by Input 1
5 | Exit 2 | 3 (+), 4 (–) | Controlled by Input 1
6 | Exit 3 | 5 (+), 6 (–) | Controlled by Input 2
7 | Exit 4 | 7 (+), 8 (–) | Controlled by Input 2
8 | Protection | — | Avoid exceeding 20mA per channel and mount in an environment free from moisture and dust.